Inspection History Details
Inspection Status: Closed
Inspection History: INITIAL CODE VIOLATION
Case Number - T01VL02419
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2001 | INITIAL CODE VIOLATION | Closed | ||
08/14/2001 | INITIAL CODE VIOLATION | Violation | IMPROPER OVERCURRENT PROTECTION AT PEDESTAL TO POWE OUTLET RECEPTACLE FOR THE MOBILE HOME LIFE LINE. OK. NEW WIRING TO NEW POST LAMP. NO PERMITS/INSPECTION WIRING NOT APPROVED FOR UNDERGROUND USE. IMPROPER WIRING METHODS EG. USING PLUMBING FITTINGS IMPROPER RACEWAY TERMINATION ETC. | |
08/14/2001 | INITIAL CODE VIOLATION | Approved | RE-SUBMIT OF INITIAL NOTICE OF VIOLATION ORGINAL LOST TO THEFT OF CITY VEHICLE ITEMS OUTLINED IN NOTICE OF VIOLATION DATED REPAIRED/ABATED IMPROPER OVER CURRENT PROTECTION: BREAKER CHANGED TO 50 AMP 2 POLE OK 2.) POST LAMP WIRING WRONG MATERIAL, NO INSPECTION REMOVED OK 3.) IMPROPER WIRING METHODS USING PLUMBING FITTINGS AND IMPROPER CONDUIT TERMINATION ABATED OK. |