Case: T01VL01763

Parcel: 11711096D


Addresses:

100 N STONE AV


Inspection Status: Correction Required

Inspection History: INITIAL CODE VIOLATION

Case Number - T01VL01763

Inspection Description - INITIAL CODE VIOLATION

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/19/2001 INITIAL CODE VIOLATION Correction Required INSPECTOR RESPONDED PER TFD ON AN EMERGENCY CALL OUT TO THE PIONEER BUILDING. N&O INDEMNIFICATION SIGNED.
CAUSE OF DAMAGE: FIRE AROUND EXHAUST SYSTEM FOR EMERGENCY ELECTRICAL SYSTEM. LOCATION IN EMERGENCY ELECTRICAL SYSTEM ROOM.
BUILDING: NEED A FACTORY APPROVED STONE AROUND EXHUAST SYSTEM. NEED TO REPLACE ROOF SYSTEM OVER GENERATOR SYSTEM.
MECHANICAL: NEED TO REPLACE FUSED SPRINKLER HEADS. THOSE W/PAINT ON THEM NEED TO BE REPLACED. F/U SCHEDULED FOR 06/21/01.