Inspection Status: Correction Required
Inspection History: INITIAL CODE VIOLATION
Case Number - T01VL01763
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2001 | INITIAL CODE VIOLATION | Correction Required | INSPECTOR RESPONDED PER TFD ON AN EMERGENCY CALL OUT TO THE PIONEER BUILDING. N&O INDEMNIFICATION SIGNED. CAUSE OF DAMAGE: FIRE AROUND EXHAUST SYSTEM FOR EMERGENCY ELECTRICAL SYSTEM. LOCATION IN EMERGENCY ELECTRICAL SYSTEM ROOM. BUILDING: NEED A FACTORY APPROVED STONE AROUND EXHUAST SYSTEM. NEED TO REPLACE ROOF SYSTEM OVER GENERATOR SYSTEM. MECHANICAL: NEED TO REPLACE FUSED SPRINKLER HEADS. THOSE W/PAINT ON THEM NEED TO BE REPLACED. F/U SCHEDULED FOR 06/21/01. |