Inspection Status: Closed

Inspection History: FOLLOW UP CODE VIOLATION

Case Number - T01VL00660

Inspection Description - FOLLOW UP CODE VIOLATION

Inspection Status - Closed

Date Description Inspector Results Comments
03/29/2001 FOLLOW UP CODE VIOLATION Closed DUCTS ARE NOW ALL SEALED.CLEANED.CLOSE CASE
03/15/2001 FOLLOW UP CODE VIOLATION Correction Required WORK IN PROGRESS- TALKED TO OWNERS AND TENANT AT SAME TIME,,TENANT IS HAPPY SO FAR, STATES SHE WILL MOVE.F/U SCHEDULE 3-29-01.
03/05/2001 FOLLOW UP CODE VIOLATION Correction Required SITE VISIT I FOUND GRILLE COVERS MISSING, ON INSPECTION OF DUCT WORK I SEEN IMPROPER SEALING OF DUCTS,ALLOWING DUST,DIRT & INSUL. TO COME INTO APT 11,ALL HEATING,COOLING & VENTING SYSTEMS MUST BE SEALED IN A PROPER MANNER.A MOLD COUNT IS NEEDED IN THIS UNIT.F/U SCHEDULE 3-15-01