Permit: T01PL02570

Parcel: 128061300


Addresses:

940 S VAN BUREN AV

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/18/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) INSTALL UNION ON T & P RELIEF DRAIN. 2.) WATER HEATER BLOCKS ACCESS TO FURNESS (FOR REMOVAL) 3.) NEW GAS PIPING BLOCK REMOVAL OF FURNESS. 1.) REMOVE BRANCH (ALL) PIPING TO FIREPLACE AND PLUG AT TEE 2.) PIPING TO SUNKEN PATIO FOR BBQ (FUTURE) IS UNKNOWN VARIABLE. NEED TO KNOW BTU CONSUMPTION. 3.) PROVIDE APPROVED ISOMETIC DRAWING SHOWING TOTAL DEVELOPED LENGTH AND BTU CONSUMPTION OFALL APPLIANCE 4.) REQUIRE 10# MINIMUM TEST ON ENTIRE SYSTEM.