Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/13/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*CORRECTIONS HAVE BEEN AMDE CALL GAS CO 889-1888. CARD AT METER SETS. |
| 12/12/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*WHO IS YOUR PLUMBER PLEASE READ OVER SEE 313.8 94UPS. APPROVED FLASHING REQUIRED JOINTS AT ROOF. 608.3 94UPC PROVIDE WORKING RELIEF VALVE W/DRAIN 514.2 94UPC VENTS SHALL BE SECURELY SUPPORTED PLEASE REMOVE TIE WIRE FASTEN IN APPROVED MANOR FASTEN JOINTS WITH SHEET METAL SCREWS OR OTHER APPROVED MEANS. PLEASE NOTE DO NOT CUT FLASHING TEST TO REMAIN ON FOR NEXT INSPECTION. |