Permit: T01PL02525

Parcel: 119033490


Addresses:

535 W 42ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS RECONNECT

Date Description Inspector Results Comments
10/17/2002 PLUMBING - GAS RECONNECT Approved IVRS - Inspection 0000*
10/14/2002 PLUMBING - GAS RECONNECT Denied IVRS - Inspection 0999*1.) WATER HTR FLU VENT MUST BE 5'-0' MIN. 2.) WATER HTR FLU VENT REQUIRES A FLASHING ON ROOF 3.) MUST HAVE MIN 1' CLEARANCE AROUND FLU VENT FROM COMBUSTIONABLE MATERIAL 4.) MUST PROVIDE AGA OR CSA APPROVED SHUT OFF VALVES FOR RANGE & WATER HTR. 5.) MUST SCREW DOWN FLU VENT WITH (3) SHEET METAL SCREWS PER JOINT 6.) PROVIDE AIR TEST 10LBS MIN.
10/03/2002 PLUMBING - GAS RECONNECT Denied IVRS - Inspection 0999*
05/08/2002 PLUMBING - GAS RECONNECT Not ready for Inspection IVRS - Inspection 0000*TEST DOWN PLEASE PROVIDE 10LBS TEST ON COMPLETE SYSTEM NO BODY HOME.
01/30/2002 PLUMBING - GAS RECONNECT Denied IVRS - Inspection 0999*
01/09/2002 PLUMBING - GAS RECONNECT Denied IVRS - Inspection 0999*1.) T & P RELIEF DRAIN MAY NOT BE PVC USE APPROVED MATERIALS. 2.) NO COMBUSTION RELIEF IN WATER HEATER ENCLOSURE.
12/18/2001 PLUMBING - GAS RECONNECT Denied IVRS - Inspection 0999*