Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T01PL02305
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2001 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* | |
11/29/2001 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection 0000*#1 TEST OK ON NEW 1" GAS LINE FROM METER TO HOUSE. OK TO BACK FILL SITE ONLY. 2.) PLEASE PROVIDE PERMIT FOR GAS FURNACE NO RECORD OF INSTALLATION. CODE VIOLATION ON VENT. WILL NEED MECH INSP BEFORE CLEARANCE IS GIVEN. 3.) ALSO CODE VIOLATION ON VENT AT WATER PLEASE PROVIDE APPROVED TYPE VENT THROU ROOF DOUBLE WALL PLEASE WITH APPROVED VENT CAP. RUN RELIEF LINE OUTSIDE. NO RECORD OF PERMIT FOR UNIT. | |
11/22/2001 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) PROVIDE ISOMETRIC FOR DEVELOPED LENGTH AND BTU LOADING FOR GAS 2.) HAVE PLUMBER CORRECT PIPING AT WATER HEATER AND DRYER. 3.) COPPER TUBE NOT APPROVED FLEX CONNECTOR 4.) EACH APPLIANCE MUST BE VALVED AND FLEXED. 5.) MOBILE HOME CONNECTOR NOT APPROVED TO CONNECT UNDERGROUND TO BLDG. 6.) TEST ENTIRE SYSTEM TO 10LBS. 7.) ALL VALVES TO BE AGA OR CSA APPROVED. 8.) NO COMBUSTION RELIEF PROVIDED. |