Permit: T01PL02305

Parcel: 10602278A


Addresses:

215 W KING RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T01PL02305

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2001 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
11/29/2001 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection 0000*#1 TEST OK ON NEW 1" GAS LINE FROM METER TO HOUSE. OK TO BACK FILL SITE ONLY. 2.) PLEASE PROVIDE PERMIT FOR GAS FURNACE NO RECORD OF INSTALLATION. CODE VIOLATION ON VENT. WILL NEED MECH INSP BEFORE CLEARANCE IS GIVEN. 3.) ALSO CODE VIOLATION ON VENT AT WATER PLEASE PROVIDE APPROVED TYPE VENT THROU ROOF DOUBLE WALL PLEASE WITH APPROVED VENT CAP. RUN RELIEF LINE OUTSIDE. NO RECORD OF PERMIT FOR UNIT.
11/22/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) PROVIDE ISOMETRIC FOR DEVELOPED LENGTH AND BTU LOADING FOR GAS 2.) HAVE PLUMBER CORRECT PIPING AT WATER HEATER AND DRYER. 3.) COPPER TUBE NOT APPROVED FLEX CONNECTOR 4.) EACH APPLIANCE MUST BE VALVED AND FLEXED. 5.) MOBILE HOME CONNECTOR NOT APPROVED TO CONNECT UNDERGROUND TO BLDG. 6.) TEST ENTIRE SYSTEM TO 10LBS. 7.) ALL VALVES TO BE AGA OR CSA APPROVED. 8.) NO COMBUSTION RELIEF PROVIDED.