Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/26/2001 |
PLUMBING - GAS PRESS TEST FNL |
|
Approved |
|
| 11/23/2001 |
PLUMBING - GAS PRESS TEST FNL |
|
Denied |
IVRS - Inspection 0999* |
| 11/21/2001 |
PLUMBING - GAS PRESS TEST FNL |
|
Denied |
IVRS - Inspection 0999*1.) WATER HTR @ REAR OF HOUSE CAN NOT HAVE A FLEX LINE IN THE P & T DRAIN. THIS LINE MUST BE FULL SIZE 3/4" FROM VALVE TO DAYLIGHT AND PROVIDE A UNION 2.) WATER HTR @ CENTER OF HOUSE P & T DRAIN MUST HAVE A 90 @ EXTERIOR WALL POINTED DOWN. 3.) MUST REMOVE ASBESTUS FLU VENT & REPLACE WITH B-VENT THRU ROOF B-VENT MUST BE DBL. WALL THRU ROOF WITH CAP AND SCREW DOWN VENT COLLAR AND ALL JOINTS WITH (3) SHEET METAL SCREWS. 4.) MUST REMOVE ALL UNIONS IN GAS LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLES TO MAKE A SOLID CONNECTION 5.) RE TEST SYSTEM 10 LBS MIN. 6.) WATER HTR HAS EXSISTING 1/2' SUPPLY. AND SHOULD BE 3/4" MIN. |