Permit: T01PL02291

Parcel: 126051320


Addresses:

4038 E 1ST ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
11/26/2001 PLUMBING - GAS PRESS TEST FNL Approved
11/23/2001 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*
11/21/2001 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*1.) WATER HTR @ REAR OF HOUSE CAN NOT HAVE A FLEX LINE IN THE P & T DRAIN. THIS LINE MUST BE FULL SIZE 3/4" FROM VALVE TO DAYLIGHT AND PROVIDE A UNION 2.) WATER HTR @ CENTER OF HOUSE P & T DRAIN MUST HAVE A 90 @ EXTERIOR WALL POINTED DOWN. 3.) MUST REMOVE ASBESTUS FLU VENT & REPLACE WITH B-VENT THRU ROOF B-VENT MUST BE DBL. WALL THRU ROOF WITH CAP AND SCREW DOWN VENT COLLAR AND ALL JOINTS WITH (3) SHEET METAL SCREWS. 4.) MUST REMOVE ALL UNIONS IN GAS LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLES TO MAKE A SOLID CONNECTION 5.) RE TEST SYSTEM 10 LBS MIN. 6.) WATER HTR HAS EXSISTING 1/2' SUPPLY. AND SHOULD BE 3/4" MIN.