Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01PL02051
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) ALL CORRECTIONS HAVE BEEN MADE. | |
| 10/25/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) C.O. TEE IS NOT A DRAINAGE FITTING. MUST USE A SAN TEE IN WALL. | |
| 10/16/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.)MUST PROVIDE C.O. FOR SINK WHERE NEW TRAP ARM & P - TRAP WAS INSTALLED 2.) CAN NOT WET VENT A 2" P-TRAP ON A 2" VERTICAL DRAIN. THE BARCEL OF VERTICAL WASTE MUST BE 1 PIPE SIZE LARGER THAN P-TRAP. 3.) TRAP WILL REQUIRE A TRAP PRIMER. 4.) MUST SEE P.O.C. OF NEW TRAP ARM TO VERTICAL WASTE. |