Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) HCS CONNECTION IS OK 3.) P.O.C. OF NEW BLDG SEWER TO EXSISTING BLDG. DRAIN IS OK 4.) OK FOR BACKFILL. |
| 10/16/2001 |
PLUMBING - FINAL |
|
Denied |