Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) ALL CORRECTIONS HAVE BEEN MADE 2.) OK FOR DRYWALL. |
| 10/23/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*109,110,111,112,209,210,211,212, 1.) ISOLATE COPPER FROM ITSELF 2.) STRAP COPPER SO IT WONT GANG IN THE WALL OR TOUCH OTHER COPPER LINES. |
| 10/18/2001 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*102,101,201,202, 1.) APT BLDG #1 UNITS #101,102,201,202, 1.) APT BLDG #1 UNITS #101,102,201,202, WATER RE-PIPE COPPER TYPE "M" 2.) COPPER REPIPE OK PRESSURE TEST OK 3.) CONTRACTOR TO INSURE ALL COPPER ISOLATED CONTRACTOR TO INSTALL VACUUM BREAKERS AT ALL HOSE BIBBS 4.0 OK TO COVER WALLS. |