Permit: T01PL01707

Parcel: 133291140

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Permit Number - T01PL01707

Inspection Description - PLUMBING - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/31/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) CAN NOT HAVE FLEX LINE IN P & T DRAIN.P & T DRAIN MUST BE FULL SIZE ALL THE WAY TO DAYLIGHT SEC SECTION 608.5 94 UPC 2.) GAS PRESSURE TEST IS OK.