Permit: T01PL01695

Parcel: 133150320


Addresses:

7001 E REDBUD RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
09/10/2001 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection 0000*1.) ALL CORRECTIONS HAVE BEEN MADE 2.) GAS PRESSURE TEST IS OK 3.) WATER HTR P & T DRAIN, FLU VENT IS OK 4.) FURNACE FLU VENT IS OK 5.) U.C.C. HAS BEEN PLACED @ METER LOCATION.
09/05/2001 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*1.)MUST HAVE A APPROVED DRANING OF GAS LINE SHOWING SIZE OF LINE AND SLEEVING UNDER PATIO SLAB. 2.) MUST PROVIDE A AGA OR CSA GAS SHUT OFF VALVE BEFORE THE UNION OR REPLACE WITH RIGHT & LEFT HAND UNION 3.) MUST HAVE 1" RISER @ METER 4.) RETEST THE SYSTEM 10LBS MIN @ TIME OF INSPECTION. 5.) MUST EXTEND FLU VENT 1"-0" ABOVE COOLER.
08/31/2001 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*1.)NO ONE HOME. I MUST HAVE ACCESS TO ALL GAS APPLIANCES INSIDE DWELLING. PLEASE CALL 791-5550 IF YOU NEED TO MAKE A APPOINTMENT.