Permit: T01PL01565

Parcel: 127120080


Addresses:

5532 E 7TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/14/2001 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*1.) GAS PRESSURE TEST OK 2.) GAS SHUT OFF VALVES ARE OK 3.) WATER HTRS FLU VENT, PT DRAIN IS OK 4.) ALL CORRECTIONS HAVE BEEN MADE 5.) U.C.C. HAS BEEN PLACED @ METER LOCATION.
08/13/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*MUST REMOVE UNION IN 1/2" GAS LINE IN FURANCE RM #2 IN MAIN HALL AND REPLACE WITH RIGHT & LEFT HAND NIPPLE SEE SECTION 1211.10.94 UPC 2.)MUST RUN HARD PIPE THRU HOUSING OF FURANCE #2 AS REQUESTED SEE SECTION 1212.0 SUB NOTE #2.
08/09/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.)MUST STRAP DOWN ENTIRE GAS LINE WITH APPROVED STRAPS. 2.) MUST SCREW DOWN ALL JOINTS AND VENT COLLAR FOR WATER HTR FLU VENTS. 3.) MUST HARD PIPE THRU FURANCE THEN CONNECT FLEX CONNECTOR. 4.) MUST SECURE 1/2" GAS DROP FOR WATER HTR IN HOUSE.