Permit: T01PL01507

Parcel: 133040190

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01PL01507

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) OVERHEAD GAS SYSTEM IS OK 3.) GAS SHUT OFF VALVES IS OK 4.) WATER HTR FLU VENT, P & T DRAIN IS OK 5.) GAS PACK IS ON ROOF. 6.) U.C.C. HAS BEEN PLACED @ METER LOCATION.
07/31/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) MUST REMOVE ALL UNION IN LINE. YOU MAY USE A RIGHT & LEFT HAND NIPPLE IN LOW OF UNION.2.) MUST HAVE 1" GAS PIPE UP TO 1ST TEE FOR AC UNITS ON ROOF.3.) MUST REMOVE P&T FLEX LINE AND RUN FULL SIZE 3/4 DRAIN TO EXSISTING P&T DRAIN. 4.) MUST SCREW DOWN ALL FLU VENT JOINTS AND VENT CONNECTOR WITH 3 SCREWS 5.) RE-TEST.