Permit: T01PL01424

Parcel: 11301061B


Addresses:

1519 E ALLEN RD

Inspection Status: Partial Approval

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
04/04/2002 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*1.) PROVIDE APPROVED REVISED PLAN. 2. CONTRACTOR WILL PROVIDE AIR TEST ON SITE SEWER VACUUM TEST REQUIRED AT MANHOLE. 3.) PROVIDE VARIFICATION OF GRADE OK TO BACKFILL SUBJECT TO ABOVE.
04/03/2002 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*PLEASE SEE LAST REQUEST .
04/01/2002 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*#1.) PROVIDE APPROVED PLAN ON JOB 2.) WILL REQUIRE VARIFICATION OF GRADE. 3.) REMOVE TEC & PROVIDE APPROVED FITTINGS PROVIDE FITTING WITH SWEEP. #4.) WILL REQUIRE AIR TEST OR WATER TEST. 5.) PROVIDE LISTING ON TRANSISSION FITTINGS FROM SDR 35 DIP. #6.) PROHIBITED FITTING SADDLE.