Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*CORRECTIONS HAVE BEEN MADE FIRE PLACE HAS BEEN ABANDON TEST OK ON COMPLETE SYSTEM. |
| 07/27/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) VENT FOR OVER PASSES THRU Z COMBUSTIBLE PARTITIONS REPLACE WITH DBL WALL AND PROVIDE CLEARANCE 2.) PROVIDE CLEARANCE AROUND COMBUSTIBLES AT WATER HEATER 3.) FITTINGS COVERED ON UNDERGROUND PIPING EXPOSE ALL FITTINGS. 4.) A GROUND JOINT UNION MAY BE INSTALLED IN AN EXPOSED EXTERIOR LOCATION, WHEN PRECEEDED BY AN APPROVED BLDG SHUT OFF VALVE 5.) FREE STANDING FIRE PLACE HAS BEEN PERMANENTLY DISCONNECTED. |
| 07/11/2001 |
PLUMBING - FINAL |
|
Not ready for Inspection |
1.) PLEASE SEE SEC 313.8 94 UPC GAS PIPING PASSING THRU ROOF REQUIRE A FLASHING 2.) SEE TABLE 3.1. HANGER OR SUPPORT INTERVALUES #3. SEE STANDARD ON FIELD WRAP PIPE PRIMER 4.) SEE SEC 517.6 VENTING TERMINATION PROVIDE PROPER CLEARANCE FROM COOLER 5.) SEC 608.5 RELIEF LINE TRAPPED. 6.) PROVIDE LISTING FOR FREE STANDING FIRE PLACE CODE VIOLATION AN VENT THROU ROOF IF LISTED PROVIDE DOUBLE WALL ROOF. |
| 07/10/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*NO ONE HOME! I CAN NOT WAIT. |