Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01PL01347
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) 2" HORIZONTAL VENT HAS EXCEEDED MAY ALLOWABLE DISTANCE 2.) WASTE AIR TEST 5 IBS OK 15 MIN. 3.) P.O.C. OF 2" WASTE IS OK. | |
07/06/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) N/H CAST IRON TO BE SUPPORTED WITHIN 18" EACH SIK OF COUPING AND EVERY CHANGE OF DIRECTION 2.) PLUMBERS TAPE NOT APPROVED STRAP. 3.) CORRECT BACKPITCH ON VENT 4.) PROTECT COPPER FROM OTHER METALS. |