Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/16/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) ALL CORRECTIONS HAVE BEEN MADE 2.) U.C.C. HAS BEEN PLACED @ METER LOCATION. |
| 07/30/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) GAS PRESSURE TEST IS OK 2.) OK TO BACKFILL TRENCH 3.) WATER HTR P&T DRAIN MUST EXTEND TO 6" A.F.F. 4.) MUST REMOVE SINGLE WALL FLU VENT AND REPLACE WITH DBL WALL B-VENT & CAP 5.) MUST SCREW DOWN ALL FLU VENT JOINTS (3) SCREWS EACH AND @ VENT CONNECTOR 6.) MUST HAVE AGA SHUT OFF VALVE FOR RANGE. |