Permit: T01PL01036

Parcel: 106121950


Addresses:

1621 W KILBURN ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
06/26/2001 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection 0000*CORRECTION MADE TEST ON COMPLETE SYSTEM OK THANKS CALL GAS CO 889-1888
06/21/2001 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection 0000*1.) PROVIDE A PRESSURE TEST OF NOT LESS THEN 10LBS ON COMPLETE SYSTEM 2.) PRIME & WRAP ALL JOINTE UNDER GROUND 3.) PROVIDE VALUE BEFORE UNION 4.) APPROVED LISTED VALUES REQUIRED AT EACH FIXTURE 5.) RELIEF LINE NET TO CODE RUN TO OUTSIDE