Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T01PL01032

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*1)FINAL CONNECTION TO EXSISTING 1/2 GAS LINE IS OK.2)OK TO PATCH CEILING AND INTERIOR WALL.
06/13/2001 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*1. GAS PRESSURE TEST OK 2. WATER HTR FLU VENT, P& T DRAIN OK.3. OVERHEAD WATER DISTRIBUTION OK 4. WATER HTR ENCLOSURE OK 5. NOTE: MUST SEE THE FINAL CONNECTION OF NEW 1/2" GAS LINE TO EXISTING. PLEASE CALL ME TO SET A TIME.
06/11/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1)PLAN SHOWS 1/2" GAS LINE TO WATER HEATER YOU CAN NOT GO FROM 1/2" TO
3/4" REMAIN 1/2" ALL THE WAY TO RELOCATION OF WATER HEATER.2)MUST USE GALV. TWO HOLE STRAPS ON GAS LINE.3)WATER HEATER P AND T DRIAN MUST TERMINATE 6" ABOVE SUB GRADE OR 24' MAX.4)MUST HAVE 1" CLEARANCE AROUND DBL WALL FLU VENT FROM WOOD.AT ROOF PENETRATIONS AND BEAM.5)MUST PRESSURE TEST GAS LINE (NEW 1/2" LINE ONLY) 10 LBS MIN.6)MUST
SCREW DOWN FLU. VENT JOINTS WITH (3) SHEET METAL SCREWS.