Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01PL00971
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
05/10/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) PRESSURE TEST 20# OK 2) THREAD PROTECTORS ARE NOT APPROVED FITTINGS REPLACE WITH AN APPROVED COUPLING AND RETEST TO 10# 3) PLUMBERS TAPE IS NOT AN APPROVED STRAP-USE 2 HOLE STRAPS 4) ALL VALVES AND FLEXES MUST BE AGA APPROVED 5) COMBUSTABLES STORED TOO CLOSE TO WATER HEATER |