Permit: T01PL00645

Parcel: 133421650

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/05/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
04/04/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) MUST USE SPECIALIT COUPLINGS AT POC OF NEW BLDG DRAIN 2) MUST USE SOLID P TRAP AT A. WASHER 3) PROVIDE WATER TEST
04/02/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) MUST PROVIDE WATER TEST ON WATE AND VENT SYSTEM 2) FERNCO COUPLING IS APPROVED FOR EXTERIOR OF STRUCTURE ONLY. MUST USE SPECIALITY COUPLING
3) MUST USE DIRECTIONAL FITTING ON HORIZONTAL WASTE LINE (COMBO, L-SWEEP) 4) MUST SECURE COPPER LINES IN WALL. COPPER CAN NOT TOUCH EACH OTHER DUE TO TRANSFER OF HEAT. 5) P TRAP FOR A.W. MUST BE 6" A.F.F. STAND PIPE CAN ONLY BE 18" MIN. 30" MAX SEE SEC 804.1 94 UPC
6) HORIZONTAL VENT MUST BE 6" ABOVE FLOOD RIM LEVEL SEE SEC. 905.3 94 UPC 7) KITCHEN SINK CONTINUOUS WASTE NOT TO CODE
03/28/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) NO ONE HOME. ANA ADULT MUST BE PRESENT FOR INSP.