Permit: T01PL00571

Parcel: 10705113A


Addresses:

502 W LAGUNA ST #13

Inspection Status: Approved

Inspection History: PLUMBING - GAS RECONNECT

Date Description Inspector Results Comments
04/27/2001 PLUMBING - GAS RECONNECT Approved IVRS - Inspection 0000*
04/17/2001 PLUMBING - GAS RECONNECT Denied IVRS - Inspection 0999*
03/12/2001 PLUMBING - GAS RECONNECT Denied IVRS - Inspection 0999* 1) UNDER GROUND GAS TO BE BURIED 18" DEEP 2) UNDRE GROUND PIPE MUST BE FACTORY COATED 3) JOINTS OF UNDER GROUND PIPE MUST BE WRAPPED WITH 40MIL TAPE (USE PRIMER ALSO) 4) NO DIELECTRIC UNION 5) NO FLEX CONNECTOR 6) YOU NEED TO INSTALL SHUT OFF VALVES FOR ALL GAS FIRED APPLIANCES 7) SHEET ROCK WALLS AND CEILING OF WATER HEATER CLOSET WITH 5/16" OR 1/2" DRYWALL.