Permit: T01PL00568

Parcel: 14024044E


Addresses:

1240 E GANLEY RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/19/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
03/15/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999* 1) ALL NEW PIPING INSTALLED 6" ABOVE GRADE AND BELOW TO BE SCOTCHCOAT. 2) ALL NEW GAS PIPING TO BE A MINIMUM OF 12" BELOW GRADE. 3) BRASS REPAIR COUPLING NOT APPROVED FOR GAS. 4) NO UNIONS USE RIGHT AND LEFT HAND NIPPLES AND COUPLINGS 5) ALL VALVES TO BE AGA OR CSA APPROVED (STAMPED IN VALVE BODY)