Permit: T01PL00561

Parcel: 137070400


Addresses:

521 W UTAH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/16/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*/1. (65') SIXTY FIVE FEET OF 1" PVC PIPING INSTALLED. 2. (10') TEN FEET OF COPPER PIPING INSTALLED. 3. TRENCH DEPTH: 14 INCHES 4. WATER PRESSURE: 50 PSI. 5. (2) TWO ANTI SIPHON DEVICES INSTALLED. 6. ELECT. SERVICE HAS TWO GROUNDING CONDUCTORS. ONE IS BONDED TO THE WATER LINE AT THE WATER HEATER. THE OTHER GOES INTO THE EARTH UNDER THE METER PANEL. NO VISIBLE GROUND RODS.
03/12/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* ALL WORK ALREADY COVERED