Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T01PL00548
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2001 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000*1.) PRESSURE TEST OK 2.) *NOTE 1.) PRESSURE TEST TENPOUND OR LESS SHALL BE PERFORMED WITH GAUGES OF 1/10 POUND INCRUMENT 2.) PRESSURE TESTS EXCEEDING 10LBS BUT LESS THAN 100LBS SHALL BE PERFORMED WITH GAUGES OF ONE POUND INCREMENTATION OR LESS 2.) PIPING INSTALLED UNDER THIS CONTRACT OK 3.) OK FOR GAS 4.) THERE ARE EXISTING SYSTEMS TIED INTO THE MAIN THAT DO NOT MEET CODE REQUIREMENTS I RECOMMEND THAT SOME ONE REVIEW THESE SYSTEMS AND INITIATE CORRECTIONS. | |
07/31/2001 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection 0000* |