Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/08/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) MUST REMOVE ALL UNIONS IN LINE AS REQUESTED AND REPLACE WITH RIGHT AND LEFT HAND NIPPLE SEE SEC 1211.10 94 UPC (ON ROOF) 2) MUST PERMANANTLY CAP SHUT OFF VALVE IN WALL FURNACE FOR WEST SUITE 3) MUST HAVE ROOF FLASHING WHERE GAS LINE PENETRATES ROOF 4) WATER HEATER P AND T DRAIN CAN ONLY HAVE A MAX OF 12" FLEX IN LINE. SEE SEC 608.0 CITY OF TUCSON MODIFICATIONS | |
| 03/05/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) MUST REMOVE ALL UNIONS IN GAS LINE AND REPLACE WITH RIGHT AND LEFT HAND NIPPLES SEE SEC 1211.10 94 UPC 2) MUST STRAP DOWN GAS LINE WITH APPROVED STRAPS TO UNISTRUT ON ROOF 3) ADD A STRAP TO GAS LINE THAT FEEDS WATER HEATER AND FURNACE ROOM 4) WATER HEATER P AND T DRAIN MUST GO TO DAYLIGHT 5) WATER HEATER #2 FLU VENT MUST BE SCREWED DOWN WITH 3 SHEET METAL SCREWS ON ALL JOINTS AND COLLAR 6) WATER HEATER #2 MUST HAVE SHUT OFF VALVE ON BRANCH SERVING WATER HEATER |
|
| 03/02/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* NO ONE HOME |