Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01PL00448

Parcel: 126120090


Addresses:

330 N BELVEDERE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/02/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
02/28/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) REMOVE ALL 10 MIL TAPE AND TAPE PRIMER ALL FITINGS AND WRENCH MARKS THEN RE TAPE LEAVE OLD 10MIL TAPE BY TRENCH 2) MUST PAY REFEE BEFORE NEXT INSP.
02/26/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) GAS FITTINGS THAT ARE UNDERGROUND MUST FIRST HAVE TAPE PRIMER THEN 10MIL TAPE