Permit: T01PL00411

Parcel: 128071780


Addresses:

6001 E 18TH ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/14/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) THE FLU PIPING NEEDS 3 SCREWS INSTALLED IN ALL JOINTS PER CODE
2) EXHAUST PIPING IS TRAPPED. DRAIN VALVE MUST BE INSTALLED AT THE LOWEST POINT OF THE PIPING