Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/16/2001 | PLUMBING - FINAL | Denied | ||
| 03/02/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) NO ONE HOME! I MUST HAVE ACCESS TO ALL GAS APPLIANCES INSIDE DWELLING 2) IT APPEARS THAT NONE OF THE CORRECTIONS I HAVE REQUESTED WERE MADE 3) MUST PAY REINSP. FEE BEFORE NEXT INSP. |
|
| 02/28/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) MUST REMOVE TRANSITE FLU VENT FOR WATER HEATER AND INSTALL DBL WALL FLU VENT AND SCREW DOWN FLU VENT TO COLLAR AND ALL JOINTS 2) WATER HEATER DRAIN MUST GO TO DAYLIGHT 3) WATER HEATER ENCLOSURE MUST HAVE 2 10X10 GEILLS FOR COMBUSTION 12" AFF AND 12" FROM TOP OF WATER HEATER 4) NOTE:IF YOU REPLACE W/H YOU MUST PULL A PERMIT FOR THIS INSTALLATION 5) GASLINE MUST BE 6" ABOVE SLAB CAN NOT HAVE 1" GASLINE JUST LAYING ON TOP OF CONCRETE SEE SECTION 1211.3 94 UPC 6) CAN NOT HAVE FLEX LINE GOING INTO A/C GAS PACK HOUSING SEE SEC. 12120 SUB NOTE #2 94 UPC 7) MUST HAVE A LICENCED PLUMBING CONTRACTOR DO ANY WORK ON GAS SYSTEM STATE REQUIREMENT |