Permit: T01PL00401

Parcel: 137282060

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/27/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
02/22/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) ALL GAS PIPE BELOW GRADE SHALL BE SCOTCH COAT 2) PIPE SHALL NOT BE BENT OR STRAINED 3) WHERE UNIONS ARE NECESSARY, RIGHT LEFT NIPPLES AND COUPLINGS SHALL BE USED 4) NEED TO SEE AN AIR TEST OF 10LBS 5) FITTINGS AND MARRIED PIPE NEED TO BE PRIMED AND TAPED (10MIL.)