Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/27/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/22/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) ALL GAS PIPE BELOW GRADE SHALL BE SCOTCH COAT 2) PIPE SHALL NOT BE BENT OR STRAINED 3) WHERE UNIONS ARE NECESSARY, RIGHT LEFT NIPPLES AND COUPLINGS SHALL BE USED 4) NEED TO SEE AN AIR TEST OF 10LBS 5) FITTINGS AND MARRIED PIPE NEED TO BE PRIMED AND TAPED (10MIL.) |