Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) CAN NOT HAVE PVC EXPOSED AT 90 DEGREES FOR SUPPLY AND RETURN AT SOFTNER 2) CAN NOT SCREW COPPER INTO PLASTIC, PLASTIC MAY NOT BE SCREWED INTO COPPER 3) CROSS CONNECTION AT DISCHARGE DRAIN INTO SANITARY DRAIN IS NOT TO CODE SEE SEC. 202.0, 603.0 94 UPC CAN NOT BORE A HOLE INTO WASTE LINE TO CONNECT DISCHARGE DRAIN |