Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2001 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* REQ'D SCOTCHCOAT PIPE BELOW GRADE UP TO 6" ABOVE GRADE FITTINGS AND MARRIED PIPE TO BE PRIMED AND TAPED PIPE TO BE MINIMUM 12' BELOW GRADE NEED 10# AIR TEST MINIMUM FOR 15 MINUTE VALVES TO BE AGA OR CSA APPROVED NO UNIONS IN LINE |