Permit: T01PL00082

Parcel: 126120100


Addresses:

340 N BELVEDERE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/23/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
GAS PRESSURE TEST OK
GAS SHUT OFF VALVES OK
WATER HEATER P&T DRAIN, FLU VENT OK
FURNACE FLU VENT OK
ALL CORRECTIONS HAVE BEEN MADE
01/19/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1. GAS LINE FROM METER TO HOUSE SERVICE IS UNDERSIZED THIS LINE MUST BE MIN, 1" SEE TABLE 12-3 94 UPC
2. MUST SCREW DOWN SINGLE WALL FLU VENT WITH (3) SHEET METAL SCREWS AT WATER HEATER COLLAR AND ALL FLU VENT JOINTS
3. WATER HEATER P&T DRAIN MUST HAVE DRAIN VALVE INSTALLED IN LINE, THERE CAN BE NO TRAPED WATER
4. SHUT OFF VLAVE FOR DRYER MUST BE WITHIN 3'-0" FROM APPLIANCE CONNECTION SEE SECTION 1211.15 94 UPC
5. GAS SYSTEM MUST HAVE MIN 10 LBS OF PRESSURE AT TIME OF INSPECTION
01/16/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
I MUST HAVE ACCESS TO ALL GAS APPLIANCES
PLEASE CALL 791-5550 TO MAKE A APPOINTMENT
CAN NOT HAVE ANY UNIONS IN LINE OR PROVIDE APPROVED GAS SHUT OFF VALVE BEFORE NION MUST USE APPROVED COUPLINGS ON GAS LINE, THREAD PROTECTORS ARE NOT APPROVED COUPLING
NOTE: MUST HAVE A LICENSE PLUMBING CONTRACTOR TO WORK ON GAS SYSTEM IF THIS IS A RENTAL PROPERLY, (STATE REQUIREMENT)