Permit: T01PL00049

Parcel: 132102580

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/11/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
PRESSURE TEST 10#
PIPING OK
OK TO COVER
APPLIANCES OK
OK FOR GAS
01/10/2001 PLUMBING - FINAL Denied GAS PIPE MUST BE A MINIMUM 12" BFG
WHERE DIVERGENT PIPING MEETS, THE CONNECTION SHALL BE MADE WITH A RIGHT-LEFT HAND COUPLING AND NIPPLE, A UNION MAY BE USED IN AN EXTERIOR ACCESSIBLE LOCATION ONLY WHEN PRECEEDED BY A BLDG SHUT OFF VALVE
UNABLE TO VISUALLY INSPECT VALVE FOR FURNACE MUST BE AGA APPROVED
NO COMBUSTION RELIEF IN WATER HEATER CLOSET
NO DRAIN ON T& P RELIEF DRAIN LINE