Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2001 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* PRESSURE TEST 10# PIPING OK OK TO COVER APPPLIANCES OK OK FOR GAS |
|
| 01/10/2001 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* GAS PIPE MUST BE A MINIMUM 12" BFG WHERE DIVERGENT PIPING MEETS, THE CONNECTION SHALL BE MADE WITH A RIGHT-LEFT HAND COUPLING AND NIPPLE, A UNION MAY BE USED IN AN EXTERIOR ACCESSIBLE LOCATION ONLY WHEN PRECEEDED BY A BLDG SHUT OFF VALVE UNABLE TO VISUALLY INSPECT VALVE FOR FURNACE MUST BE AGA APPROVED NO COMBUSTION REFIEF IN WATER HEATER CLOSET NO DRAIN ON T&P REFIEF DRAIN LINE |