Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2002 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000* |
| 04/15/2002 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0935*THE SIGN ON FRONT OF BLDG. STILL TIED INTO INDOOR LIGHTING CIRCUIT. PROVIDE LOAD CALCULATIONS SHOWING THAT THE 20 AMP. CIRCUIT WILL HANDLE THE INDOOR LIGHTING AS WELL AS THE SIGN MAY REQUIRE AN ELEC. ENGINEER MULTIPLE INSPECTIONS HAVE BEEN MADE WITHOUT ANY PROGRESS PAY A REINSPECTION FEE PRIOR TO NEXT VISIT. |
| 04/01/2002 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999*IDENTIFY DEDICATED SIGN CIRCUIT IN SUBPANEL RECALL FOR INSPECTION. PROVIDE LOAD CALCULATIONS IF USING A LIGHTING CIRCUIT TO POWER SIGNS. BE SURE TO LABEL ALL CIRCUIT BREAKERS FOR SIGNS. |
| 03/21/2002 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/21/2002 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999* |