Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 01/10/2002 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000* |
| 12/31/2001 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) HAVE LICENSED ELECTRICIAN COMPLETE PRIMARY WIRING TO NORTH SIGN THEN RECALL FOR INSPECTION. 2.) EAST & WEST SIGNS OK. |
| 12/26/2001 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT READY |