Inspection Status: Not ready for Inspection
Inspection History: SIGN ELECTRIC
Permit Number - T01OT01069
Inspection Description - SIGN ELECTRIC
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2002 | SIGN ELECTRIC | Not ready for Inspection | 1.) PRIMARY WIRING MUST BE COMPLETED BEFORE SIGN MAY BE FINISHED. 2.) HAVE AN L-11 LICENSED ELECTRICIAN COMPLETE THE WIRING, THEN RECALL INSPECTION. | |
01/03/2002 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) BUTTONS FOR PK HOUSING NOT INSTALLED ON NEON ELECTRODE ENDS. 2.) FLEXIBLE METAL CONDUIT IN EXCESS OF 3 1/2 MUST BE SECURED WITHIN 12" OF EACH. TERMINATION AND FOR EVERY 3 1/2' OF LENGTH. 3.) PRIMARY WIRING TO SIGN MUST BE COMPLETED 4.) JUNCTION BOXES MUST BE SECURED 5.) IDENTIFY SIGN CIRCUITS @ SUBPANEL. | |
12/27/2001 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000* |