Permit: T01OT01069


Addresses:

2 W GRANT RD

Inspection Status: Not ready for Inspection

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
01/11/2002 SIGN ELECTRIC Not ready for Inspection 1.) PRIMARY WIRING MUST BE COMPLETED BEFORE SIGN MAY BE FINISHED. 2.) HAVE AN L-11 LICENSED ELECTRICIAN COMPLETE THE WIRING, THEN RECALL INSPECTION.
01/03/2002 SIGN ELECTRIC Denied IVRS - Inspection 0999*1.) BUTTONS FOR PK HOUSING NOT INSTALLED ON NEON ELECTRODE ENDS. 2.) FLEXIBLE METAL CONDUIT IN EXCESS OF 3 1/2 MUST BE SECURED WITHIN 12" OF EACH. TERMINATION AND FOR EVERY 3 1/2' OF LENGTH. 3.) PRIMARY WIRING TO SIGN MUST BE COMPLETED 4.) JUNCTION BOXES MUST BE SECURED 5.) IDENTIFY SIGN CIRCUITS @ SUBPANEL.
12/27/2001 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*