Inspection Status: Not ready for Inspection
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 01/11/2002 |
SIGN ELECTRIC |
|
Not ready for Inspection |
1.) PRIMARY WIRING MUST BE COMPLETED BEFORE SIGN MAY BE FINISHED. 2.) HAVE AN L-11 LICENSED ELECTRICIAN COMPLETE THE WIRING, THEN RECALL INSPECTION. |
| 01/03/2002 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999*1.) BUTTONS FOR PK HOUSING NOT INSTALLED ON NEON ELECTRODE ENDS. 2.) FLEXIBLE METAL CONDUIT IN EXCESS OF 3 1/2 MUST BE SECURED WITHIN 12" OF EACH. TERMINATION AND FOR EVERY 3 1/2' OF LENGTH. 3.) PRIMARY WIRING TO SIGN MUST BE COMPLETED 4.) JUNCTION BOXES MUST BE SECURED 5.) IDENTIFY SIGN CIRCUITS @ SUBPANEL. |
| 12/27/2001 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000* |