Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2007 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 11/15/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* WALL SIGNS? NEED WALKWAY TO ACCESS BOXES 1. ISOLATE PRIMARY CONDUCTORS IN RACEWAY 2. SWITCH TO BE AS PER 600.6 3. FILL UNUSED OPENINGS IN BACK OF LETTERS 110.12 4. INSTALL AND FILL OUT MARKING LABELS 600.4 5. NEED PAPERWORK TO IDENTIFY SIGNS TO PLANS & PERMITS 6. PLEASE VERIFY POWER & CIRCUIT AS PER 600.5 |
|
| 11/14/2007 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY JOHN |
|
| 12/17/2001 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000*NOT READY "SAFE WAY" SELF CONTAINED NEON REQUIRES 2 CIRCUITS. |