Permit: T01OT00923

Parcel: 120076790


Addresses:

3919 S 12TH AV #01

Inspection Status: Denied

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
01/10/2002 SIGN ELECTRIC Denied IVRS - Inspection 0999*1.) EMT CONDUIT ACROSS ROOF MUST SUPPORTED EVERY 10' OR LESS O BLOCKS OR STAND OFFS FROM ROOF. 2.) BREAKS & DISCONNECTIONS IN CONDUIT MUST BE REPAIRED. 3.) NEUTRAL LUG IN TIME CLOCK MAY NOT BE USED AS MULTIPLE TERMINATION POINT. TIE NEURTRALS TOGETHER WITH ONLY 1 LINE UNDER LUG. 4.) PROPERLY SECURE CONDUIT FROM SERVICE PANEL ALL ALONG BACK WALL. 5.) EXTERIOR PLUG RECEPTACLES MSUT BE GFI PROTECTED. 6.) PROPERLY INSTALL DEAD FRONT PANEL AT SERVICE AND IDENTIFY SIGN CIRCUIT.
12/17/2001 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*2 X 5 FLOURESCENT "NATIONAL INSURANCE"