Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T01OT00661
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
11/14/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.)PRIMARY SIDE NOT PROPERLY BONDED TO GROUND. YOU MAY NOT USE FLEX AS A GROUNDING CONDUCTOR). 2.) RE-MOUNT 1ST AND 2ND PRIMARY J-BOXS SO THEY ARE SECURE. 1ST J-BOX NEEDS TO BE BROUGHT INTO SOFFIT AREA & HAVE PROPER COVER. ALSO BOND GROUNDING CONDUCTOR TO J-BOXES. | |
10/19/2001 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000*NOT READY TRES AMIGOS PAN CHANNEL. |