Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T01OT00621
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
11/01/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*NEC 600-5 ELECTRIC SIGN IS REQUIRED TO BE ON ITS OWN CIRCUIT WITH NO OTHER LOAD. 2.) REPLACE COVER PLATE ON J-BOX. | |
10/24/2001 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection 0000*ELECTRIC FINAL PARTIAL 1. ALL SIGN COMPONENTS OK BUT PRIMARY WIRE NOT YET INSTALLED TO J-BOX AT TRANSFORMERS. |