Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2001 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000* |
| 10/15/2001 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999*1.) ELECTRICIAN WHO INSTALLED PRIMARY WIRE FOR SIGN HAS NOT PROPERLY SECURED THE JUNCTION BOX (IT WAS ATTACHED TO A LOOSE PIECE OF 2 X 4.) 2.) MC CABLE MAY NOT BE LOOSELY STREWN ABOUT CEILING. CABLE MUST BE SUPPORTED OFF OF SUSPENDED CEILING AND THE 15' OR 20' OF EXCESS CABLE SHOULD BE SECURED OR REMOVED. BOTH CORRECTIONS LISTED ABOVE ARE ON THE PRIMARY WIRING FROM SUB PANEL. |
| 10/11/2001 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999*370-4 METAL JUNCTION BOXES SHALL BE GROUNDED 370-23 A JUNCTION BOXES TO BE RIGIDLY AND SECURLY FASTENED IN PLACE 334-10 MC CABLE SHALL BE SECURED WITHIN 12" OF TERMINATION POINTS AND AT INTERVALS NOT EXCEEDING 6' 370- ONE AT THE J-BOXES IS MISSING ITS COVERS. |
| 08/17/2001 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000* |