Permit: T01MH00570

Parcel: 136176430


Addresses:

8654 E CHASE PL

Inspection Status: Approved

Inspection History: MOBILE HOME ELECTRICAL

Date Description Inspector Results Comments
12/14/2001 MOBILE HOME ELECTRICAL Approved
11/29/2001 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000*INTERIOR PANEL BOX: THE GREEN GROUND CONDUCTOR MUST BE ON THE SAME TERMINAL STRIP AS THE GROUND WIRES. IT CANNOT BE ISOLATED.
11/27/2001 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000*PARTIAL METER PANEL OK INTERIOR PANEL, THE NEUTRAL AND GROUND TERMINAL STRIPS MUST BE ISOLATED FROM EACH OTHER.