Inspection History Details
Inspection Status: Approved
Inspection History: MOBILE HOME ELECTRICAL
Permit Number - T01MH00523
Inspection Description - MOBILE HOME ELECTRICAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2001 | MOBILE HOME ELECTRICAL | Approved | AC DUCT MUST BE 4" ABOVE EARTH. | |
11/26/2001 | MOBILE HOME ELECTRICAL | Partial Approval | IVRS - Inspection 0000*1.) DOUBLE LUGING AT MAIN PANEL 2.) SPLIT BOLT HAS TO MANY CONDUCTOR; SHOULD BE RUN & TAP ONLY. (CHECK INTO REPLACING SPLIT BOLT WITH A MULTI LUG ASSEMBLY. 3.) FEEDER JUMPERS UNDERSIZED. | |
11/20/2001 | MOBILE HOME ELECTRICAL | Denied | IVRS - Inspection 0999*1.) DOUBLE LUGING AT SERVICE PEDISTAL. 2.) SPLIT BOLT LISTED FOR RUN & TAP ONLY. 3.) BONDING JUMPER UNDER SIZED 4.) FEEDER JUMPERS UNDER SIZED. 5.) BONDING GROUNDS NEED TO BE CONNECTED TO NEUTRAL. |