Inspection Status: Approved
Inspection History: MOBILE HOME ELECTRICAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/14/2001 |
MOBILE HOME ELECTRICAL |
|
Approved |
AC DUCT MUST BE 4" ABOVE EARTH. |
| 11/26/2001 |
MOBILE HOME ELECTRICAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) DOUBLE LUGING AT MAIN PANEL 2.) SPLIT BOLT HAS TO MANY CONDUCTOR; SHOULD BE RUN & TAP ONLY. (CHECK INTO REPLACING SPLIT BOLT WITH A MULTI LUG ASSEMBLY. 3.) FEEDER JUMPERS UNDERSIZED. |
| 11/20/2001 |
MOBILE HOME ELECTRICAL |
|
Denied |
IVRS - Inspection 0999*1.) DOUBLE LUGING AT SERVICE PEDISTAL. 2.) SPLIT BOLT LISTED FOR RUN & TAP ONLY. 3.) BONDING JUMPER UNDER SIZED 4.) FEEDER JUMPERS UNDER SIZED. 5.) BONDING GROUNDS NEED TO BE CONNECTED TO NEUTRAL. |