Permit: T01MH00519

Parcel: 10706002D

Inspection Status: Approved

Inspection History: MOBILE HOME ELECTRICAL

Permit Number - T01MH00519

Inspection Description - MOBILE HOME ELECTRICAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2001 MOBILE HOME ELECTRICAL Approved A.C. DUCT MUST BE 4" ABOVE EARTH
11/26/2001 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000*1.) DOUBLE & TRIPLE LUGING AT MAIN PEDESTAL. 2.) SPLIT BOLT HAS TO MANY CONDUCTORS: TRY MULTI LUG ASSEMBLY. 3.) FEEDER JUMPERS UNDER SIZED.
11/20/2001 MOBILE HOME ELECTRICAL Denied IVRS - Inspection 0999*1.) DOUBLE LUGING & TRIPLE LUGING AT MAIN PEDISTAL 2.) SPLIT BOLTS LISTED FOR RUN & TAP ONLY 3.) CLEAN SURFACE UNDER LUG 4.) CAN NOT USE SHEET METAL SCREW FOR GROUNDING.