Inspection History: MOBILE HOME ELECTRICAL
Permit Number - T01MH00519
Inspection Description - MOBILE HOME ELECTRICAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2001 | MOBILE HOME ELECTRICAL | Approved | A.C. DUCT MUST BE 4" ABOVE EARTH | |
11/26/2001 | MOBILE HOME ELECTRICAL | Partial Approval | IVRS - Inspection 0000*1.) DOUBLE & TRIPLE LUGING AT MAIN PEDESTAL. 2.) SPLIT BOLT HAS TO MANY CONDUCTORS: TRY MULTI LUG ASSEMBLY. 3.) FEEDER JUMPERS UNDER SIZED. | |
11/20/2001 | MOBILE HOME ELECTRICAL | Denied | IVRS - Inspection 0999*1.) DOUBLE LUGING & TRIPLE LUGING AT MAIN PEDISTAL 2.) SPLIT BOLTS LISTED FOR RUN & TAP ONLY 3.) CLEAN SURFACE UNDER LUG 4.) CAN NOT USE SHEET METAL SCREW FOR GROUNDING. |