Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01MH00442

Parcel: 111031160

Inspection Status: Approved

Inspection History: MOBILE HOME UNDERGROUND GAS

Date Description Inspector Results Comments
09/05/2001 MOBILE HOME UNDERGROUND GAS Approved IVRS - Inspection 0000*
08/31/2001 MOBILE HOME UNDERGROUND GAS Denied IVRS - Inspection 0999*1.) GAS UNION BELONGS ON DISCHARGE SIDE OF SHUT OFF VALVE. 2.) GAS GAUGE NEEDS TO READ IN 1/10 LB INCREMENTS 3.) DO UNDERGROUND TEST AT 15 PSI. 4.) USE PROPER COUPLING ON GAS LID.