Inspection History Details
Inspection Status: Approved
Inspection History: MOBILE HOME ELECTRICAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2001 | MOBILE HOME ELECTRICAL | Approved | IVRS - Inspection 0000*GROUNDING CORRECTIONS HAVE BEEN MADE. | |
| 07/25/2001 | MOBILE HOME ELECTRICAL | Denied | IVRS - Inspection 0935* | |
| 07/16/2001 | MOBILE HOME ELECTRICAL | Partial Approval | IVRS - Inspection 0000*PEDESTAL OK GROUNDING CONDUCTOR PARTIAL CANNOT BE SPLICED MUST RUN CONTINUOUS FROM METER THRU BOTH GROUND RODS. EXPOSE TOPS OF GROUND RODS FOR INSP. | |
| 06/01/2001 | MOBILE HOME ELECTRICAL | Denied | IVRS - Inspection 0999*1)IMPROPER WIRING CONNECTION AT SWAMP COOLER.2)ELECTRIC WILL NOT BE CLEARED UNTILL PEDISTAL HAS BEEN APPROVED.3)PEDISTAL REQUIRES SEPERATE PERMIT AND NEW GROUNDING ELECTRODE SYSTEM AND ADDRESS PERMANENTLY MARKED ON PEDISTAL (ENGRAVED OR METAL TAG) |